Owner correction: Harper’s room is Bedroom 3, not Bedroom 4. Lower-window alignment remains provisional until the large Oriel and possible Great Room upper-window removal are shown together. See the corrected current plan images.
November 8,2026 · Full comparison of Alyssa’s November 6 attachment, the permit and later drawings, current whole-house R28, all 23 derived room meshes, and the registered detailed studies.
The current models are not fully aligned with this order, and the order is not a complete, unambiguous house-wide shop-drawing release. Several supplier changes are clear; other items conflict or are absent. This audit identifies exactly what to update and what must be clarified. No existing model, approval or order has been overwritten.
I opened the live Gmail attachment and downloaded it. Its bytes match the archived supplier PDF exactly: Elite order A30-00583, reference OA30-00-0583,14 pages. It contains 26 active line items totaling 29 units/assemblies. Cancelled item numbers 8,9 and 29 are not active supply rows.
The order was created October 2; its header says last modified October 19; the pages were printed November 4 at 09:34 and Alyssa sent them November 6. These are different dates, not proof of a further November 6 manufacturing revision. The printed required date is December 7,2026, shipped to Muskoka Lumber. It is not confirmation of delivery to the cottage.
The comparison uses the sealed July 22 permit set (A101/A102 floor plans, A103 roof, A200/A201 elevations and schedules, A300 sections, structural sheets), October 6 revised window elevations, later Oriel v1.3, current November 3 bathroom study and the current R28 mesh. I checked source documents, actual numeric faces and the 23 derived room meshes; their hashes and clipped geometry agree with R28. That proves coordination with the parent model, not agreement with the newer order.
Four different measurements must remain separate: the product’s outside frame, the opening needed in framing (rough stud opening), the larger concrete/ICF opening with its buck, and the visible glass/daylight. A difference between two of these is not automatically an error. Many assembled units in this order do not state their rough opening at all.
The findings that matter most
Resolve the duplicated TW107 before manufacture or installation is treated as verified. Page 12 lists quantity 2 of 60×28⅞in under TW106/TW107, then another quantity 1 of 60×30 in under TW107. There are three units but only two known tags. R28 has two 60×24 in openings. Neither the duplicate nor the extra height has been resolved in the model.
The Great Room window wall needs a complete shop-elevation check. The order has two roughly 145⅛ in-wide,96 in-high lower banks. R28’s six lower glass faces are 108 in high. Glass cannot be 12 in taller than the entire supplied frame. The upper-bank heights differ as well. Their detailed corner dimensions imply 1:12, while assembly text says 4.5/12 and 5.7/12. Do not change the repaired roof or structural supports to follow those contradictory labels; place the complete lower/upper assemblies on the architectural section datum first.
The primary bathroom still uses the old windows. W103 is ordered 25×60 in, not 25×48 in. W104 is 72×96 in at the floor, with 26 in lower slider and 70 in fixed upper. Both the current R28 bathroom and its November 3 standalone study retain 72×90 in at a 6 in sill and a 30 in rail. This needs a window-only reconciliation; the 74 in double vanity and tower removal stay.
Michelle’s windows are 99 in wide in the order,102 in in the October 6 elevations and R28. W101/W102 need actual 74 in fixed /25 in operator divisions, not the current two-thirds split. The taller floor-to-head 96 in direction is already incorporated.
The front/south powder and boot-room windows materially change. W110 changes 24×36 to 25×54 in. W111 changes 48×36 to 25×54 in. Keeping their 96 in head gives a 42 in sill, consistent with the kitchen, but sill and corner-reveal placement must be confirmed.
The basement lake windows need different widths and divisions. W003 is 138 15/16 in,5 1/16 in narrower than the 144 in model. W004/W005 are 145⅛ in,1⅛in wider. All use 36 in casements; the model’s 24 in-looking flankers are wrong. Supplier feasibility of 36×80 in operators and upper/lower jamb alignment needs written closure.
W007 and the Muskoka exterior door E102 are not listed. They still exist in the plans/current model. Do not silently delete them. Confirm separate supply, retagging or omission. The supplier’s email says only the main entry, E101 and bay remain outstanding, so these absences need explanation.
E004 has four legitimate dimension layers to coordinate.36 in nominal door slab,38 in ordered frame,39 in normal rough opening and 44 in ICF opening in the email. The missing buck/detail must explain the difference. This is not automatically a 5 in mistake.
The kitchen’s 25 in flankers already agree with the attachment. The email also says 24 in elsewhere. Keep the current 25/94/25 study while Matt/Alyssa correct the contradictory wording.
“Final” still excludes major selections. The main entry is a separate Mastergrain item, the Great Room/Muskoka connection is to be ordered after walls/site visit, and W107 bay is explicitly removed from this order. The additional Harper window remains an owner question, not an approved added opening.
What changes in each model family
Model / image family
Finding and consequence
Whole-house R28 and 23 derived room models
All 23 files match their manifest hashes. Their faces are exact or geometrically clipped from R28 within 0.0001 in. They inherit its window discrepancies. Regenerate affected room extracts and exterior cameras together after the parent is reconciled.
Registered Great Room detailed source
R28 registers the older R13 room with later local corrections. W109, CW1 and high side windows still need the order reconciliation. The three south clerestories TW103–105 have no explicit matching tagged glazing faces in the current mesh; their representation cannot be certified from source metadata alone.
Kitchen standalone and R28 integration
W112 modules already 25/94/25 and 54 high, at 42 sill. Preserve it and the counters, sink, hood, appliances and enclosed storage. Model frame/reveal dimensions are not the supplier’s clear-glass dimensions.
November 3 primary bathroom standalone and R28 integration
Both retain the old W103/W104 envelopes. Revise both from one source change; do not revise just a photograph or revert the bathroom interior.
Bedroom 1 legacy room study and current house room
The older study already records XOX operation but uses traced widths, older upper heights and an obsolete interior-transom note. Reconcile E100/TW100–102 and retain the historic approvals only for their original bytes/scope.
November 8 timber comparison
Isolated R28-derived variants changed timber profiles/materials and adopted the later 80 in-high,three-part Oriel preference. They did not update the canonical master or reconcile this final window order. They remain useful edge/finish comparisons, not window certifications.
Published exterior/interior photographs and saved cameras
Retain all originals. Add a superseding window-reconciled version after model review. Saved camera angles may carry forward as views, but existing photographic geometry does not become approved by reuse. Recheck mullions, sightlines, furniture/privacy, roof junctions and adjoining-room visibility.
The audit does not authorize manufacturing, construction, purchases or a new owner approval. I have prepared a version-bound change list rather than mixing unresolved order conflicts into an already repaired master model. Download proposed model changes.
Every opening and its disposition
33 comparison entries cover all 26 active supplier lines, grouped assemblies, cancellations and expected-but-absent items. “Change” includes detailed frame/division updates; “Coordinate” means a datum or order conflict must be settled before exact geometry is chosen.
Permit 102 x 80, sill 16; Oct 6 elevation 102 x 96, sill 0
Final order
99 x 96;74 fixed +25 operator over 25 x 24 fixed
Current model
R28 plan/mesh 102 x 96. Divider at 2/3 gives 68+34, not 74+25. Floor-height direction is applied.
Finding
Change required:3 in narrower than Oct 6/model. This is a source reconciliation, not evidence of a changed room wall.
Next action
Use 99-inch supplier frame in a new version; replace divider with 74/25 and correct outside-view handing. Obtain assembly rough opening; retain location until jamb alignment is confirmed.
Permit 102 x 80, sill 16; Oct 6 elevation 102 x 96, sill 0
Final order
99 x 96;74 fixed +25 operator over 25 x 24 fixed
Current model
R28 plan/mesh 102 x 96. Divider at 2/3 gives 68+34, not 74+25. Floor-height direction is applied.
Finding
Change required:3 in narrower than Oct 6/model. This is a source reconciliation, not evidence of a changed room wall.
Next action
Use 99-inch supplier frame in a new version; replace divider with 74/25 and correct outside-view handing. Obtain assembly rough opening; retain location until jamb alignment is confirmed.
Order change not yet incorporated in either bathroom model.
Next action
Increase height 12 in. If head 96 is retained, sill becomes 36 in; this is an inferred placement requiring designer confirmation against WC/privacy and current I104.
Supplier PDF page(s): 7
Model or detail change
Primary bathroom · bathtub window (W104) · Primary bathroom tub
Architectural baseline
72 x 90, sill 6, head 96
Final order
72 x 96 at floor; fixed 70 in above 26 in slider
Current model
R28 and Nov 3 standalone 72 x 90 at 6 sill; rail 30 above floor
Finding
Change required. Retain all unrelated November 3 interior layout.
Next action
Lower sill 6 in to floor; move rail from 30 to 26 in, upper fixed 70 in. Check bath/window adjacency and privacy without changing 74 in vanity or removed tower. Assembly rough opening remains absent.
Supplier PDF page(s): 6, 7
Keep / already reflected
Chris’s bedroom · side window near bathroom (W105) · Bedroom 1 · Chris
Architectural baseline
25 x 60, sill 36
Final order
25 x 60 left casement; rough 26 x 61
Current model
R28 nominal 25 x 60, sill 36; historic standalone has traced 25.5/25.6 in apertures
Finding
No confirmed nominal size change. Old study dimensions are not a supplier frame definition.
Next action
Retain nominal envelope and sill. Add product operation/handle; distinguish traced rough/daylight from 25 in unit.
Supplier PDF page(s): 6
Keep / already reflected
Chris’s bedroom · side window near lake (W106) · Bedroom 1 · Chris
Architectural baseline
25 x 60, sill 36
Final order
25 x 60 left casement; rough 26 x 61
Current model
R28 nominal 25 x 60, sill 36; historic standalone has traced 25.5/25.6 in apertures
Finding
No confirmed nominal size change. Old study dimensions are not a supplier frame definition.
Next action
Retain nominal envelope and sill. Add product operation/handle; distinguish traced rough/daylight from 25 in unit.
Permit 71.5 x 72/sill 24; later v1.2=94.625 x 90; v1.3=94.625 x 80, centre 66.625 +14+14
Final order
Excluded explicitly; separate bay remains TBD
Current model
Canonical R28=94.625 x 90 single glass; timber study only uses 80 high three-part v1.3
Finding
Master remains 10 in too tall relative to v1.3 working preference. Timber study does not update master.
Next action
Use v1.3/owner casement preference for next working-design reconciliation, but do not claim ordered. Supplier feasibility, rough opening, glazing/finish and final configuration remain open.
Supplier PDF page(s): 13
Keep / already reflected
Nook · former side window (removed) (W108) · Nook side wall
Architectural baseline
Permit 24 x 72, sill 24
Final order
Cancelled October 19
Current model
R28 flat-Oriel revision removes former side window
Finding
Decided deletion already reflected in current house.
Next action
Keep removed. Retain bookcase on unchanged nook wall.
Supplier PDF page(s): 13
Model or detail change
Great Room · small side-wall window (W109) · Great Room side/exterior
Architectural baseline
Permit 24 x 72/sill 24
Final order
27 x 72 right casement; rough 28 x 73
Current model
Actual R28 glass 24 x 72 at 24 sill
Finding
Change required; current Great Room detailed source and derived room also 24 wide.
Next action
Widen nominal unit 3 in; retain sill/head pending rough-opening/location coordination; verify jamb and adjacent siding.
Supplier PDF page(s): 2
Model or detail change
Boot room · front window (W110) · Boot room
Architectural baseline
24 x 36/sill 60/head 96
Final order
25 x 54; rough 26 x 55
Current model
R28 plan/mesh 24 x 36/sill 60
Finding
Change not applied. Email match-to-W112 direction supports head 96/sill 42 inference.
Next action
Widen 1 in and raise height 18 in. Keeping head 96 implies sill 42 in, which matches kitchen alignment; confirm head datum and cabinetry.
Supplier PDF page(s): 1
Model or detail change
Powder room · front window (W111) · Powder room
Architectural baseline
48 x 36/sill 60/head 96
Final order
25 x 54; rough 26 x 55
Current model
R28 plan/mesh 48 x 36/sill 60
Finding
Change not applied; significant south-elevation appearance difference.
Next action
Narrow 23 in; increase height 18 in. Keeping head 96 implies sill 42 in. Confirm outside corner reveal/jamb anchor instead of assuming centred placement.
Supplier PDF page(s): 1
Keep / already reflected
Kitchen · sink window (W112) · Kitchen
Architectural baseline
144 x 54/sill 42; later approved 25/94/25 study
Final order
144 x 54,25/94/25; email also says 24 in flankers
Current model
Standalone kitchen and R28 both 25/94/25, sill 42/head 96; modeled reveals 145 x 55 are not unit dimensions
Finding
Geometry already matches attachment nominal modules. Do not change to 24 in flankers.
Next action
Keep current supplier-sized divisions. Ask supplier/builder to remove 24 in wording conflict; add correct handedness and contemporary cranks to detailed representation.
R28 plan/mesh 144 x 80;24/96/24 nominal module ratios
Finding
Required change with alignment clarification; do not force glass/frame/rough jambs into equality.
Next action
Narrow 5.0625 in and use actual 36 in flankers. Overall 139-frame-class unit is 0.25 in narrower than E100139.1875 above: obtain intentional jamb/mullion datum.
Supplier PDF page(s): 9, 10
Model or detail change
Rec Room · lake window below living area (W004) · Rec room · lake
Architectural baseline
144 x 80/sill 16
Final order
145.125 x 80;36/72.875/36 plus couplers
Current model
R28 plan/mesh 144 x 80;24/96/24 divisions
Finding
Change required. Overall upper/lower frame widths differ only 0.003 in using the detailed 3686.1 mm dimension (0.007 in using rounded 3686 mm); this is rounding, not a real alignment defect.
Next action
Widen 1.125 in; use 36 in flankers and actual couplers. Supplier must confirm 36 x 80 casement limits; align to 145.122 in CW1 frame above using physical frame/rough datums.
Supplier PDF page(s): 10, 11
Model or detail change
Rec Room · lake window below dining area (W005) · Rec room · lake
Architectural baseline
144 x 80/sill 16
Final order
145.125 x 80;36/72.875/36 plus couplers
Current model
R28 plan/mesh 144 x 80;24/96/24 divisions
Finding
Change required. Overall upper/lower frame widths differ only 0.003 in using the detailed 3686.1 mm dimension (0.007 in using rounded 3686 mm); this is rounding, not a real alignment defect.
Next action
Widen 1.125 in; use 36 in flankers and actual couplers. Supplier must confirm 36 x 80 casement limits; align to 145.122 in CW1 frame above using physical frame/rough datums.
Change required; do not silently keep 24 in sill and raise head to 104 in.
Next action
Widen 3 in and increase height 8 in. Preserving head 96 gives 16 in sill; order itself does not state mounting height. Confirm sill, egress and deck/ground relation.
Unresolved omission; supplier email lists other outstanding units but not W007.
Next action
Confirm omission, cancellation, retagging or separate supply. Do not delete window merely because it is absent from order.
Supplier PDF page(s): Not an active supply row; see email/scope review
Coordinate before geometry change
Great Room · complete lake window wall (CW1) lower · SB001/SB002 · Great Room lake
Architectural baseline
A200/A300 traced six-pane lower bank; structural station governs
Final order
Two 3686 x 2438 mm three-panel banks; about 145.118 x 95.984 in
Current model
R28 six glass faces each 108 in high, from 1.92 to 109.92 above floor; two banks about 145 in wide
Finding
Current window wall is not a certified match to final order. Glass already exceeds supplier whole-frame height, so frame allowances cannot explain 12 in.
Next action
Reconcile the 12 in lower-height difference as an assembly: finished floor/sill, frame/glass, intermediate steel/mullions and upper geometry. Do not lower/raise roof or beams from this comparison alone.
Supplier PDF page(s): 3
Coordinate before geometry change
Great Room · complete lake window wall (CW1) upper · SB100/SB101 · Great Room lake
Architectural baseline
A200/A3001:12 roof stations; current model follows sloped upper openings
Final order
3686 mm banks; high/low corners 1752.6/1445.4 mm and 1393.8/1086.6 mm
Current model
R28 upper glass heights west 53.56/49.533/45.5 in, east 39.513/35.487/31.46 in; common base 115.92 above floor
Finding
Coordinate, not automatic roof redesign. Per-frame declared slope 1/12 agrees with detailed corner differences.
Next action
Obtain a tagged shop elevation placing each bank on the section datum. Detailed dimensions give 1:12 fall; assembly labels 4.5/12 and 5.7/12 contradict that. Verify SB100/101 bank orientation and supports.
Use actual frame and unequal upper widths; rough width difference 0.1875 in is within old 0.67 in tracing uncertainty, not evidence framing is wrong. Actual field rough opening still required.
Replace widths and sloped heights while keeping roof and structural positions until vertical placement verified. Align to actual E100 panel/mullion locations. Do not assume sill 103 still works.
Supplier PDF page(s): 5
Coordinate before geometry change
Great Room · left high window over entry roof (TW103)–Great Room · right high window over entry roof (TW105) · Kitchen/entry high south clerestory
Architectural baseline
45.5 each; high edges 20.25/24.125/27.875; sill 144
Final order
45.5 each; high edges 21.375/25.125/28.875
Current model
No explicit tagged opening records in R28 plan; actual geometric candidates must be traced by location
Finding
Cannot certify as present/correct solely from source-plan metadata. Needs explicit face-to-tag mapping.
Next action
Add tag bindings; compare candidate south clerestory geometry to current 1:12 sections. Nominal tallest-height increase 1 in (TW103+1.125 in) versus schedule. Confirm mounting datum.
Supplier PDF page(s): 11, 12
Coordinate before geometry change
Great Room · high side window nearer entry (TW106)/Great Room · high side window nearer lake (TW107) · Great Room high side glazing
Architectural baseline
60 x 24 each, sill 144
Final order
Item 25 qty 2 at 60 x 28.875; item 26 qty 1 labelled TW107 at 60 x 30
Current model
R28 has two explicit 60 x 24 faces at 144 sill
Finding
Order has 3 units for 2 known tags. Cannot pick 28.875 or 30 in for TW107 without confirmation.
Next action
Supplier must resolve duplicate TW107 tag/extra unit and intended locations before changing heights. Retain two openings pending answer.
Supplier PDF page(s): 12
Keep / already reflected
Interior transoms INT100/101 · Bedroom/hall
Architectural baseline
Permit two 30 x 24 above interior doors
Final order
Item 29 cancelled October 8
Current model
R28 door openings reach 96; no distinct INT100/101 glazing; historical bedroom 1 record still mentions transom
Finding
Current house deletion agrees; legacy record text not fully reconciled.
Next action
Keep deletion in active model. Mark older room/source documents superseded; do not mistake a 96 in doorway head for transom glazing.
Supplier PDF page(s): 13
Excluded / missing / decision pending
Main entry E103/E104/E105 · Front entry
Architectural baseline
Permit 24+36+24 x 96 assembly
Final order
Separate Mastergrain fibreglass/app lock, not included
Current model
R28 generic 84 x 96 entry assembly; no exact Mastergrain shop profile
Finding
Excluded scope, not proved missing from procurement.
Next action
Keep as explicitly provisional; obtain separate ordered unit and exact frame/rough opening. Do not label generic three-part mesh the final order.
Supplier PDF page(s): Not an active supply row; see email/scope review
Excluded / missing / decision pending
Great Room ↔ Muskoka Room folding doors (E101) · Great Room ↔ Muskoka room
Architectural baseline
Permit 96 wide; later owner rough-framing 131.75 wide, north-folding three-leaf
Final order
To be ordered after walls/site visit; email 131.75 in framing
Current model
Current integration has later owner connection; supplier final frame not yet ordered
Finding
Later design change is in working model; final shop unit not included.
Next action
Retain owner same-level floor/north-fold direction. Confirm clear/frame/rough widths and threshold with field opening; supplier question about floor level is already answered by owner direction.
Supplier PDF page(s): Not an active supply row; see email/scope review
Potential scope omission; not a deletion instruction.
Next action
Confirm separate door/screen supply or retagging; supplier says only main entry/E101/bay remain, so omission needs explicit closure.
Supplier PDF page(s): Not an active supply row; see email/scope review
Model or detail change
Basement · lake walkout below Oriel (E002) · Basement lake walkout
Architectural baseline
71.5 x 95.5
Final order
70.625 x 95.5 frame; rough 71.625 x 96; XO
Current model
R28 aperture 71.5 x 95.5; no shopframe distinction
Finding
Small frame/rough-vs-nominal distinction, not 0.875 in proven construction shortfall.
Next action
Model actual frame/rough opening separately.0.125 in width difference between model aperture and rough is below trace uncertainty; no claim of wrong concrete opening.
Supplier PDF page(s): 11
Coordinate before geometry change
Basement · side entrance door (E004) · Basement west entry
Architectural baseline
36 x 95.5 nominal door
Final order
38 x 95.5 overall frame;39 x 96 normal rough; email 44 in ICFrough
Current model
R28 generic 36 wide glazing/opening
Finding
Email/attachment dimensions need buck-detail reconciliation, not a blind 5 in framing error conclusion.
Next action
Represent 36 slab/38 frame/39 rough/44ICFblockout as distinct datums. Obtain buck thickness, tolerances and anchoring detail; never enlarge 36 slab to 44.
Supplier PDF page(s): 13
Excluded / missing / decision pending
Additional Harper window · Bedroom 4
Architectural baseline
Not in permit or current window inventory
Final order
Still asked as an owner question November 6; no additional order row
Current model
R28 has existing W001, no newly approved extra opening
Finding
Not authorized by this audit and not included in final order. Existing W001 is not the additional request.
Next action
Use latest November 3 discussion: one additional window remains under consideration, no extra rec-room windows. Await owner direction and marked foundation location/quote.
Supplier PDF page(s): Not an active supply row; see email/scope review
Order quality, operation and installation checks
Handing is drawn from outside. W101/W102 place the operating modules on different sides; a text “left opening” and an assembly position are not the same thing. R28 uses generic glazing for many openings. Do not reverse a product by reading an exterior shop view as an interior view.
Couplers matter. W003’s 36+66 11/16+36 modules total 138 11/16 in, but the supplied assembly is 138 15/16 in. The extra¼in is in the assembly/coupling system. Likewise W004/W005 modules sum 144⅞in while the whole frame is 145⅛ in. The order’s 3686 mm upper width converts to 145.118 in, practically the 145.125 in lower frame within rounding; do not flag that 0.007 in as a real defect.
Product frame is not visible glass. Exact sash sightlines, clear opening, hinge reach, insect screens and cranks are not all modeled. W104’s lower slider has an expressly unwarranted painted-black interior finish. The email says the owners are aware/okay; this report does not create a new acceptance record. Retain that exception with the product documentation.
Egress and safety glazing require the actual installation. The order marks certain casements/sliders as egress and calls for tempered glass in several large/floor-level units. Those labels do not establish actual unobstructed clear opening, finished sill height, window-well clearance, hardware access or compliance on site. Ask for the relevant supplier performance/detail sheets and designer/builder verification.
Site installation and delivery are separate from ordering. Several large sealed units ship loose; some screens/operators are not installed. Confirm glass handling, reinforcement/couplers, bucks, fastening, air/water detailing, tolerances and the coordinated delivery/install sequence. Page 1’s December 7 required date is a supplier milestone, not a booked cottage installation. No final price, revised total, freight amount or confirmed site delivery appointment is present in this 14 page attachment.
The lower casement alignment needs a defined target. W003 is¼in narrower than the actual E100 frame above. Is the intended match between outer frame jambs, rough jambs, mullions or visible glass? Obtain one marked elevation instead of shifting our masonry, roof or windows to an undefined “align.”
Who needs to act
Alyssa / Matt / supplier
Issue one corrected tagged shop package resolving duplicate TW107, W007 and E102 scope, CW1 slopes/bank orientation and the 24/25 in kitchen wording.
Provide all assembly frame and rough openings, outside-view handing, sill/head datums and lower/upper alignment drawing; confirm 36×80 casement feasibility.
Show the E004ICF/buck/frame section; confirm delivery, loose-glass handling and installation scope.
Keep the main entry, E101 andbay as explicit separate orders with their own final records.
Meghan / Nada / structural designer
Reconcile bathroom W103/W104 with November 3I104 and privacy/tub details, preserving the approved interior direction.
Place CW1 upper/lower banks, high clerestories and structural steel on the A300 roof/ceiling datums; verify that supply fits before changing any roof.
Confirm inferred 42 in W110/W111 sills,16 in W006 sill if retaining 96 in heads, and corner reveal/jamb locations.
Chris / Michelle
Decide whether the one additional Harper/Bedroom 4 window proceeds, using a marked location and complete installed quote. The November 2 email’s earlier two-window wording was narrowed in the November 3 discussion; no new rec-room openings are inferred.
Final main entry, Oriel configuration and Muskoka connection remain in their separate review paths. Reviewing this report does not approve the supplier order.
Our modeling work
Use the attached parent-bound change list. Apply confirmed changes in a new working plan, compare 2Dwith sources, rebuild 3Dand room extracts, test adjoining views, then seek the normal owner review. Hold only the affected component when a datum is unresolved.
Retain R28, existing studies and all prior images/approvals. Regenerate photographs from the reviewed next model, not by painting new mullions onto old images.
Detailed geometry checks and source fingerprints
Exact supplier attachment SHA256: f062a87599ab7009e5bef6197e2aba6ea32fdfea6ca03c4cd219bb1ebf94d391. Current parent model SHA256:0a6e9f338bfcab7c0a90ede51208dc3c4e2a878d51075442363d77d583a34b0a.
No physical site measurements, manufacturing release, structural approval or new live owner decisions were made. Historical models and photos are retained; this report does not independently recertify every archived version.